Warmup 6iE WiFi Thermostat manual


Warmup 6iE WiFi Thermostat manual Image

WiFi Thermostat

The smartest, most efficient way to control the world’s best selling floor heating

Pack Contents

Safety Information

  • The 6iE must be installed by a qualified electrician. It requires a permanent 230 V AC supply from a 30mA RCD or RCBO protected circuit in accordance with the current edition of the BS7671 Wiring Regulations.
  • Isolate the 6iE from the main supply throughout the installation process.
    Ensure that wires are fully inserted into the terminals and secured, free strands should be trimmed, as they could cause a short-circuit.
  • Install the 6iE in an area with good ventilation. It should not be beside a window/door, in direct sunlight, or above another heat-generating device (e.g. radiator or TV).
  • Ensure the distance from your router to the 6iE is not excessive. This will ensure the wireless connection is not subject to range issues once installed.
  • For bathroom installations, the 6iE MUST be mounted outside of Zones 0, 1, and 2. If this is not possible then must be installed in an adjacent room, controlling the rooms using a remote sensor(s).
  • The 6iE and its packaging are not toys; do not allow children to play with them. Small components and packaging present a risk of choking or suffocation.
  • The 6iE is suitable for indoor use only. It must not be exposed to moisture, vibrations, mechanical loads, or temperatures outside of its rated values.
  • For safety and licensing reasons (CE/UKCA), unauthorized change and/or modification of the 6iE is not permitted.

Step 1 – Installation

Isolate the 6iE supply from the mains supply.

Unclip the display from the power base.

Release the display as shown.

Install a 50 mm deep electrical back box in your preferred thermostat location. Pull wires (heater, supply, and sensor(s) through the backbox and complete terminal wiring.

Step 2 – Wiring Connections

WARNING!
The 6iE must be installed by a qualified electrician in accordance with the current edition of the BS7671 Wiring Regulations. Wire the 6iE using the diagram above and the heater-type wiring information below.

NOTE: For loads above 10 A, the conductor wire gage should be at least 2.5mm²

ELECTRIC UNDERFLOOR HEATING
L1 & N4 Heater Live and Neutral Max. 16A (3680W)
L2 & N3 Supply Live and Neutral
5 & 6 * Floor Sensor (No Polarity)

HYDRONIC UNDERFLOOR HEATING
L1 Switched Live to Wiring Centre
L2 & N3 Supply Live and Neutral
N4 Not Used
5 & 6 * Floor Sensor (No Polarity)
* Floor sensor connection;
5 & 6 Scheduled floor temperature with air limit
6 & 7 Scheduled air temperature with a floor limit
Refer to Appendix 1.0 for alternative thermostat use cases

CENTRAL HEATING
L1 Switched Live to Zone Valve/Boiler
L2 & N3 Supply Live and Neutral
N4 Not Used
5 & 6 Not Used
For extra low voltage or volt-free systems, a contractor must be used.
Connecting the 6iE directly to extra-low voltage or volt-free boilers may cause damage to the boiler circuit.

Step 3 – Thermostat Mounting

Insert fixing screws through mounting holes of the power base and tighten.

Re-attach the display until a “click” is heard. You can now restore power to the circuit and power up the thermostat. Follow the on-screen instructions to set up your system. Once set up a QR Code will appear.

Step 4 – Initial Setup

Download the MyHeating App.

Open the My Heating App and scan the QR Code on the 6iE screen.
Follow the instructions in the App to complete the setup.

www.warmup.co.uk

Step 5 – Add Location and Room

The heating App will guide you through the setup of your 6iE. You will have to set up your house location and then the room within which your new 6iE is located.


Location
A location needs to be set up before a room can be configured and the 6iE device registered. Creating a location is user-friendly and easy to follow, it is advised to have details of your current energy tariff and pricing to hand, as these will be required if you wish to use the energy monitoring features.


Room Setup
With a location now set up, the next step is to register a room in which your 6iE is located. This is the heating zone your thermostat will control. Ensure you set the correct System Type and Wattage of heaters connected.

NOTE: If an external relay or contactor relay has been installed please set System Type as Electric + Relay.

Welcome to the 6iE

Getting Started

How to quickly change the temperature
Use the slider or press the +/- icons to change your target temperature.
If in “Program” mode this will set a temporary override until your next heating period.
If in “Manual” mode this will set a fixed target temperature.
Once the target temperature is set above the current floor/air temperature the heating indicator will appear.

How to quickly change mode
Mode select allows you to quickly change from program, manual, or holiday modes. You can also switch “Frost Protection” on or simply switch the “Heating Off” from here. Frost protection will ensure that the floor/air temperature does not drop below 7.0°.

Heating
How to set a program
Setting a “Program” allows you to set comfort temperatures at set times throughout the day. Days can be programmed individually, all days the same or weekdays as a block and weekends as a block, the choice is yours.

To “Select additional days” press the days of the week and the squares will be highlighted in white as shown and will follow the programmed heating schedule.

Once you are happy press “Accept” to save the heating schedule.
NOTE: For tailor-made preset heating schedules for different room types press the three dots “…” on the weekly schedule page.

Setback Temperature
The “Setback” temperature is a lower energy-efficient temperature when outside of a heating period.

Heating
How to set into Manual Mode
Setting into “Manual” mode allows you to set a fixed target temperature for the thermostat to achieve. The thermostat will continue to maintain this temperature until another operating mode or temperature is selected.

Heating
How to set into Holiday Mode
“Holiday Mode” allows you to override your schedule with a lower fixed temperature over a set time to save energy.

How to switch “Heating Off”
This will switch the heating off until you cancel it by pressing “Heating Off” on the home screen or going into mode select and pressing the “Heating Off” slider.

Energy Monitor

How Energy Monitor works
The 6iE learns how you use your system and how your house reacts to heating and weather. Energy monitoring will show the amount of energy consumed over a certain time period. This will be calculated through system power multiplied by efficiency and run time.
You will need to enter the power of your system, and in some cases, the efficiency.
If you do not know these, speak to your installer or system manufacturer.

Changing the Power Settings
If you have entered the wrong system power during setup, it can be changed in Energy
Monitor; Power Settings.

SmartGeo

How SmartGeo works

SmartGeo is a unique technology developed by Warmup and built into the MyHeating App that uses an advanced algorithm to understand the most efficient heat settings for your home.
Working automatically; it learns your routines and location through background communication with your smartphone and lowers temperatures when you are away, only rising them up to your ideal comfort temperature in time for your arrival home.
Smartgeo will operate when the thermostat is in the program or manual run modes. It is turned off by default. Use the MyHeating App to switch SmartGeo on.

Settings

Language Settings Change the 6iE language
Time & Date Change the Time and Date
Daylight savings On/Off
24-hour time On/Off
Heating Preference Temperature unit °C/°F
Open window detection On/Off
The windows open detection feature is designed to switch off heating to save energy when the thermostat detects that a window or door has been opened and, the outside air temperature is significantly below the indoor temperature.
Adaptive Learning On/Off
Adaptive learning will use the historic heating/cooling rates for the time of day, historic external temperatures, and the forecast external temperatures, to work out the heating start time in order to reach the comfort time at the start of the comfort period. It will only work in Program Mode.
Network WiFi Connection On/Off
It is possible to set a new WiFi connection from here. The current network connection can also be viewed from this menu, including the signal strength.
Display Background Light Dark Random
Choose the background image of the 6iE. Random is an image selected from Warmup’s collection.
Standby style Temperature Time Minimalist
Choose what will be displayed when the 6iE goes into standby. The temperature will display current temperature;
Time will display the current time; Minimalist will show neither.
Brightness Active-Standby Night
Adjust the brightness of the 6iE screen when in Active, Standby, or Night Mode.
Display, cont’d Night period Set the Start and End period
This is the time when you usually go to bed at night and wake up in the morning. The brightness of “Night” mode will begin and end using this time.
Screen lock On/Off
Locks the 6iE screen to prevent any unauthorized changes to the 6iE. Requires a 4 digit code to access the menu or make changes.

Advanced Settings

Advanced settings Sensors & Application Internal Air Sensor Offset +/- 10°
Probe 1 Connected On/Off
Type
5, 10, 15, 100K
Offset
+/- 10°
The 6iE uses a 10K sensor. However, if using a 6iE to replace an existing thermostat you must change to the correct sensor type.
Probe 2 Connected On/Off
Type
5, 10, 15, 100K
Offset
+/- 10°
If a 2nd sensor is wired into terminals 6 & 7 it must be switched on here to act as a limit sensor.
Floor thermostat
(Probe 1 On, Probe 2 Off. See Appendix 1.0 for alternative thermostat use cases)
Control Floor Remote Air Regulator Limit None/Air
Choose to switch the method of control for the sensor; floor sensor, remote air sensor if not installed underneath the floor or regulator mode.
Regulator Mode; Heating is on for X% out of control cycle (default 10mins). The heating is off for the remaining time.
Floor-type* Tile/Stone
Laminate
Carpet
Wood
Vinyl
Other
Choose the floor type of your installation. This will apply different temperature and overheat limits to the 6iE.
* Not applicable if the conventional heating system was selected.
Advanced settings Temperature limits Set Min./Max. settable temperature limits
Overheat limit Set Overheat air limit if floor sensor has been installed
Control Period Set between 10 – 60 mins.
Control period checks the difference in the current measured temperature and the set temperature in a proportional-integral algorithm to maintain a steady temperature.
About Details about the 6iE’s current firmware, MAC address, and WiFi connection information.

Troubleshooting

Display is blank Brightness 1. Check that the standby brightness is not set to Off.
Power 2. (Electrician Required) Electrician required to verify power is going to the 6iE and that it is correctly wired.
ER1 Sensor Error (Electrician Required) Electrician required to verify that the floor sensor has been wired correctly. If it is correctly wired the electrician will need to check the resistance of the floor sensor using a multimeter. For temperatures between 20°C – 30°C the resistance of the floor sensor should measure between 8K ohms and 12K ohms.
If the electrician finds a fault, and the 6iE is in the room to be heated then it can be set into “Air Mode”.
To set into “Air Mode”, go to Sensors & Application in Advanced Settings and switch the probe off.
Heating is coming on earlier than programmed times Adaptive learning On Adaptive learning will use the historic heating/cooling rates for the time of day, historic external temperatures, and the forecast external temperatures, to work out the heating start time in order to reach the comfort time at the start of the comfort period. It will only work in Program Mode.
Cannot to set above a certain temperature Floor Type Temperature Limits Delicate floor coverings need to have their temperatures limited. If the finished floor is set for wood, laminate, vinyl, etc. you are unable to set the temperature above 27°C.
WiFi Error Symbol WiFi not setup If you have not done so, download the MyHeating App, go to Settings and Network setup and follow the on-screen instructions to connect to a WiFi Network.
WiFi disconnected Follow the step above to try and to re-connect to the WiFi Network.
If the 6iE still fails to connect, see WiFi Troubleshooting.
Clock Sync Icon Time and Date not set Connect the 6iE to a WiFi network or alternatively set the time and date from the settings menu.

WiFi Troubleshooting

Before following the troubleshooting guide below please check the following:

  1. The password is WPA2 protected.
  2. The router is set to a 2.4 GHz band. (802.11 b, g, n, b/g mixed, b/g/n mixed)

NOTE: If you need to change any of the items listed above, please refer to your router manual.

Technical Specifications

Model 6iE-01-XX-YY
Operating Voltage 230 V AC : 50 Hz
Protection Class Class II
Max. Load 16A (3680W)
Rated impulse voltage 4000V
Automatic action 100,000 cycles
Disconnection means Type 1B
Pollution degree 2
Max. Ambient Temperature 0 – 40°C
Relative Humidity 80%
IP Rating IP33
Dimensions (Assembled 6iE) 90 x 115 x 39 mm
Screen size 3.5in
Sensors Air & Floor (Ambient)
Sensor Type NTC10k 3m Long (Can Be Extended To 50m)
Operating Frequency 2401 – 2484MHz
Max. Radio-Frequency Power Transmitted 20dBm
Installation Depth 50 mm Back Box
Compatibility Electric, Hydronic Underfloor Heating. Max. 16A (3680W)
Central Heating Systems
(Combi & system boilers with switch live, 230V AC input)
Er-P Class IV
Warranty 12 Years
Approvals BEAN


NOTE: Hereby, Warmup plc, declares that the radio equipment type 6iE-01-XX-YY is in compliance with the RED Directive 2014/53/EU and Radio Equipment Regulations 2017. The declarations of conformity may be consulted by scanning the QR Code or visiting www.literature.warmup.co.uk/d-o-c/6iE.

https://qrstud.io/avifxn5


Instructions for Disposal
Do not dispose of the device with regular domestic waste! Electronic equipment must be disposed of at local collection points for waste electronic equipment in compliance with the Waste Electrical and Electronic Equipment Directive.

Warranty


12 Warmup plc warrants this product, to be free from defects in the workmanship or materials, under normal use and service, for a period of twelve (12) years from the date of purchase by the consumer when installed with a Warmup heater. If at any time during the warranty period the product is determined to be defective, Warmup shall repair or replace it, at Warmup’s option.

If the product is defective, please either;

Return it, with a bill of sale or other dated proof of purchase, to the place from which you purchased it, or

Contact Warmup. Warmup will determine whether the product should be returned or replaced. The twelve (12) year warranty only applies if the product is registered with

Warmup within 30 days after purchase. Registration can be completed online at www.warmup.co.uk
This warranty does not cover removal or re-installation costs and shall not apply if it is shown by Warmup that the defect or malfunction was caused by failure to follow the instruction manuals, incorrect installation, or damage that occurred while the product was in the possession of a consumer. Warmup’s sole responsibility shall be to repair or replace the product within the terms stated above. If the 6iE is installed with a nonWarmup heater a three (3) year warranty will apply. This warranty does not extend to any associated software such as apps or portals.

WARMUP SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND, INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING, DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF ANY WARRANTY, EXPRESS OR IMPLIED, OR ANY OTHER FAILURE OF THIS PRODUCT. THIS WARRANTY IS THE ONLY EXPRESS WARRANTY WARMUP MADE ON THIS PRODUCT. THE DURATION OF ANY IMPLIED WARRANTIES, INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IS HEREBY LIMITED TO THE TWELVE-YEAR DURATION OF THIS WARRANTY.

This Warranty does not affect your statutory rights.

Appendix 1.0 – Thermostat use cases

No. Reg. Mode Probe P1
(5 & 6)
Probe P2
(6 & 7)
Control Limit Sensor Use Case
1 OFF OFF OFF Internal
Air Sensor
None The thermostat in room air temperature schedule no floor limit
2 ON FF P1
Floor Sensor
None The thermostat in/out of room floor temperature schedule floor limit
3 Internal
Air Sensor
Thermostat in room floor temperature schedule air limit
4 P1
Air Sensor
None Thermostat out of room air temperature schedule no floor limit
5 OFF ON Internal
Air Sensor
P2
Floor Limit
The thermostat in room air temperature schedule floor limit
6 ON ON P1 Floor Sensor P2 Floor Limit The thermostat in/out of room floor temperature schedule floor limit
7 P1

Air Sensor

P2
Floor Limit
Thermostat out of room air temperature schedule floor limit
8 ON OFF OFF Reg. None The thermostat in/out of room regulator schedule no limit
9 Internal Air Sensor The thermostat in the room regulator schedule air limit
10 OFF ON Reg. P2 Floor Limit The thermostat in/out of room regulator schedules floor limit

Conventional Electric underfloor heating Hydronic underfloor heating

Warmup plc
www.warmup.co.uk
[email protected]
T: 0345 345 2288
F: 0345 345 2299
Warmup GmbH
www.warmupdeutschland.de
[email protected]
T: 008000 – 345 0000
F: 04431 – 948 70 18