Schneider – ItsManual https://itsmanual.com Owner's manuals for all sorts of products Tue, 27 Jun 2023 18:19:55 +0000 en-US hourly 1 https://wordpress.org/?v=6.5.2 https://itsmanual.com/wp-content/uploads/2021/09/favicon.ico Schneider – ItsManual https://itsmanual.com 32 32 Schneider APC Back-UPS Pro BX850 Manual https://itsmanual.com/schneider/apc-back-ups-pro-bx850/ Sun, 09 Apr 2023 16:08:06 +0000 https://itsmanual.com/?p=67215 Read More...

]]>
 

APC Back-UPS Pro BX850 User Manual

Safety and General Information

Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damage.

SAVE THESE INSTRUCTIONS – This section contains important instructions that should be followed during installation and maintenance of the UPS and batteries.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • This UPS is intended for indoor use only.
  • Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.
  • Connect the UPS power cable directly to a wall outlet.
  • Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.

Failure to follow these instructions will result in death or serious injury.

Inventory

Connect the Battery

The UPS is shipped with the battery disconnected.

BX850/1000M/M-LM60

  1. Remove the battery door.
  2. Remove the battery. Connect the wire.
  3. Push the battery into the unit.
  4. Replace the battery door.

BX1350/1500M/M-LM60

  1. Remove the battery door.
  2. Remove the battery.
  3. Flip or turn the battery 180 degrees upward/downward to let green side of the label face up.
  4. Push the battery into the unit.
  5. Replace the battery door.

Install PowerChute ™ Personal Edition Software

Use PowerChute Personal Edition software to configure the UPS settings. During a power outage, PowerChute will save any open files on your computer and shut it down. When power is restored, it will restart the computer.

Note: PowerChute is only compatible with a Windows operating system. If you are using Mac OSX, use the native shutdown feature to protect your system. See the documentation provided with your computer.

Installation

Use the cable supplied with the Back-UPS to connect the data port on the Back-UPS to the USB port on your computer. On the computer, go to www.apc.com Search for “PowerChute Personal Edition” then click on “View Details” to download the latest version of PCPE software. Click the download link and select Software product. Select the appropriate operating system. Follow directions to download the software.

Connect the Equipment

Battery Backup and Surge Protected outlets

When the Back-UPS is receiving input power, the Battery Backup with Surge Protection outlets will supply power to connected equipment. During a power outage or other AC problems, the Battery Backup outlets receive power for a limited time from the Back-UPS.

Connect equipment such as printers, fax machines, scanners, or other peripherals that do not need battery backup power to the Surge Protection Only outlets. These outlets provide full-time protection from surges even if the Back-UPS is switched OFF

Operation

Power Saving Display
The display interface can be configured to be continuously illuminated, or to save energy, it can be configured to darken after a period of inactivity.

  1. Full Time Mode: Press and hold DISPLAY for two seconds. The display will illuminate and the Back-UPS will beep to confirm the Full Time mode.
  2. Power Saving Mode: Press and hold DISPLAY for two seconds. The display will darken and the Back-UPS will beep to confirm the Power Saving mode. While in Power Saving Mode, the display will illuminate if a button is pressed, it then darkens after 60 seconds of no activity.

Unit sensitivity
Adjust the sensitivity of the Back-UPS to control when it will switch to battery power; the higher the sensitivity, the more often the Back-UPS will switch to battery power.

  1. Ensure the Back-UPS is connected to AC power, but is OFF.
  2. Press and hold the P OWER button for six seconds. The L OAD C APACITY bar will flash on and off, indicating that the Back-UPS is in programming mode.
  3. Press POWER again to rotate through the menu options. Stop at selected sensitivity. The Back-UPS will beep to confirm the selection.

Front Panel Buttons and Display Interface
Use the three buttons on the front panel of the Back-UPS and the display interface to configure the Back-UPS.

Alarms and System Errors

Audible Indicators

Status Icons

System Errors
The Back-UPS will display these error messages. Except for errors F01 and F02, contact SEIT Technical Support.

Function Button Quick Reference

Troubleshooting

Specifications

Replacement Battery

The battery typically lasts for 3 to 5 years, a shorter period if subjected to frequent outages or elevated temperatures. Battery replacement parts for Back-UPS BX850M/M-LM60 is RBC17, for BX1000M/M-LM60 is APCRBC158, for BX1350M/M-LM60 is APCRBC123, and for BX1500M/M-LM60 is APCRBC124. Delaying the replacement of parts may corrode the batteries in the cartridge. Recycle spent battery cartridges.

Warranty

The standard warranty is three (3) years from the date of purchase. Schneider Electric IT (SEIT) standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to the assignment of asset tags and set depreciation schedules must declare such a need at first contact with an SEIT Technical Support representative. SEIT will ship the replacement unit once the defective unit has been received by the repair department, or cross ship upon the receipt of a valid credit card number. The customer pays for shipping the unit to SEIT. SEIT pays ground freight transportation costs to ship the replacement unit to the customer.

APC by Schneider Electric IT Customer Support Worldwide

For country specific customer support, go to the APC by Schneider Electric Web site, www.apc.com.

Select models are ENERGY STAR ® qualified.
For more information on your specific model go to www.apc.com.

This UPS is certified to comply with California Battery Charger System regulations. For more information go to www.apc.com/company/us/en/sustainability/energy-efficiency/california-battery-charger-regulations/

EMC Compliance

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

© 2017 APC by Schneider Electric. APC, the APC logo, and Back-UPS are owned by Schneider Electric Industries S.A.S. or their affiliated companies. All other trademarks are property of their respective owners.

EN 990-5813A
07/2017



]]>
Schneider S1B33894 QO and Homeline Load Centers Manual https://itsmanual.com/schneider/s1b33894-qo/ Tue, 27 Jun 2023 09:47:44 +0000 https://itsmanual.com/?p=127611 Read More...

]]>

Schneider S1B33894 QO and Homeline Load Centers

Safety Information

This bulletin contains instructions for the installation and operation of QO and Homeline load centers. It also includes installation instructions for standard and tandem branch circuit breakers. See separate instruction bulletins included with advanced function circuit breakers and accessories, when installed.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, NOM-029-STPS or CSA Z462 or local equivalent.
  • This equipment must only be installed and serviced by qualified electrical personnel.
  • Turn off all power supplying this equipment before working on or inside equipment.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Replace all devices, doors and covers before turning on power to this equipment.
  • Do not allow petroleum-based paints, solvents, or sprays to contact the nonmetallic parts of this product.
  • Before starting a wiring installation or addition, consult a local building or electrical inspector for current National Electrical Code requirements. Local codes vary, but are adopted and enforced to promote safe electrical installations. A permit may be needed to do electrical work, and some codes may require an inspection of the electrical work.
  • This equipment may not be suitable for use in corrosive environments present in agricultural buildings. See NEC 547.

Failure to follow these instructions will result in death or serious injury.

Preparation

  1. Determine the wiring or conduit requirements for the main and branch circuits, as required by local electrical codes.
  2. Select the proper cable clamp, or use other approved methods for securing the cable or conduit to the enclosure.
  3. Remove the appropriate knockouts required for installation of cable clamps or conduit (Table 1). To remove the knockouts, see Figure 1.

Table 1: Bolt-on Conduit Hubs for Outdoor Load Centers

Conduit Hub No.
3/4 in. B-075
1 in. B-100
1-1/4 in. B-125
1-1/2 in. B-150
2 in. B-200
2-1/2 in. B-250

Figure 1: Removing Knockouts

Enclosure Mounting

Surface Mounting (Indoor and Outdoor) Secure the enclosure to the wall with appropriate fasteners. Use all pre-cut holes in the back of the enclosure for mounting. See Figure 2.

Outdoor

  1. Use the sealing gaskets provided if the mounting knockout locations shown in Figure 2 are used.
  2. Use either one mounting hole at the top and two mounting holes at the bottom, or two mounting knockout holes at the top and two mounting holes at the bottom. See Figure 2.

Surface Mounting Temporarily position the enclosure with the centered tear drop hole. Secure the enclosure to the wall using the four mounting holes. Figure 2: Surface Mounting

Flush Mounting (Indoor Enclosure Only

  1.  Remove the four small mounting knockouts on the side walls for securing to sixteen inch stud walls. See Figure 3.
  2. Position the enclosure between studs so that the front edge is flush with the finished wall.
  3. Secure the enclosure to the studs through the small knockouts. See Figure 3C.
    Figure 3: Flush Mounting

Main Circuit Breaker or Main Lug Wiring

  1. Pull the conductors into the enclosure. Use approved wire clamps, conduit bushings, or other approved methods to secure the conductor to the enclosure and prevent damage to the conductor insulation.
  2. Connect the main and neutral wires.
    •  Install the main and neutral wires according to the wiring diagram on the load center.
    • Connect the service ground, equipment grounding wire, or both as required by the local electrical code.
    • Torque each connection to the value specified on the load center wiring diagram attached to the enclosure.
  3. If required by the local code, install the enclosed green neutral bonding screw through the hole in the neutral bar. Thread the screw into the hole in the enclosure and torque to the value specified on the card shipped with the bonding screw.

Branch Circuit Breaker Installation and Removal

WARNING HAZARD OF PERSONAL INJURY OR EQUIPMENT DAMAGE This equipment is designed and tested by Schneider Electric™ to performance levels which meet Underwriter’s Laboratories® (UL®) standards and Mexican Official Standards (NOM) listing. Use only Square D™ brand circuit breakers and accessories. Failure to follow these instructions can result in death or serious injury.

NOTE: See separate instruction bulletins included with advanced function circuit breakers and accessories for their installation. QOP type circuit breakers are only acceptable for use on QO plug-on neutral load centers.
Standard and Tandem Branch Circuit Breakers—Installation
NOTE: Install QOT and HOMT tandem-type circuit breakers only in single-phase load centers marked for use with tandem circuit breakers. Refer to the wiring diagram on the load center for the installation location.

  1.  Determine the wiring or conduit requirements for the branch circuit.
  2. Turn OFF (O) the circuit breaker.
    NOTE: For QOT CTL tandem only: hold the circuit breaker at 30–45° angle.
  3. Install the wire terminal end of the circuit breaker onto the mounting rail.
  4. Rotate the circuit breaker inward until the plug-on jaw fully engages the bus bar connector. Keep the bottom of the circuit breaker’s case against the mounting rail. Check the terminal end of the circuit breaker for engagement to the mounting rail.
  5. Remove the wire insulation from the branch wire as required. Install the branch wire into the load terminal of the branch circuit breaker.
  6. Torque each branch circuit breaker connection to the value specified on the circuit breaker.
  7. Torque each neutral and ground connection to the value specified on the load center wiring diagram attached to the enclosure.

Figure 4: QO Standard Circuit Breaker Figure 5: QO Tandem Circuit Breaker

NOTE: Non-class CTL tandem circuit breaker shown. QOT class CTL tandem circuit breaker (not shown) cannot be installed on a plug-on neutral load center (metal mounting rail).

Figure 6: Homeline Standard Circuit Breaker Figure 7: Homeline Tandem Circuit Breaker

Removal

  1.  Turn OFF (O) the circuit breaker. Remove the wires.
  2. To disconnect the plug-on jaw from the connector and mounting rail, lift the plug-on end of the circuit breaker until the circuit breaker jaw disconnects from the bus bar. Continue lifting until the terminal end disengages from the mounting rail. See Figure 4, 5, or 6 depending on circuit breaker type.

Installing the Cover / Trim

  1. Remove the cover twistouts. Remove the appropriate twistouts to match the number of circuit breakers being installed. See Figure 8.
  2. Attach the Spanish translation label, supplied with the load center, to the inside of the door or cover. See Figure 9.
  3. Identify the circuit breakers on the directory label.
  4. For service equipment, apply the “Service Disconnect” label(s) near the disconnect handle(s). If the main circuit breaker is installed and the device is used as a branch panel, apply the “Main” label to the trim near the main circuit breaker handle. See Figure 9.
  5. Install the trim/cover using the screws provided and torque to 20 lbs-in. (2.3 N•m).
  6. For QO outdoor load centers that are 150–225 A single-phase, main lug devices rated for 22,000 RMS symmetrical amperes short circuit systems, use four screws by removing the interior trim support bracket knockout. See Figure 9.
  7. Fill any unused circuit breaker opening with the filler plates.
  8. Figure 8: Remove Twistouts
  9. Figure 9: Label Locations

Energizing the Load Center

  1. Before energizing the load center, turn off the main and all branch circuit breakers.
  2.  After power is turned on to the load center, turn on the main circuit breaker and then turn on the branch circuit breakers.
  3. Rotate the door latch counterclockwise to allow engagement through the door slot (outdoor only).
  4. Close the door until secured by the latch.

Schneider Electric USA, Inc. 800 Federal Street Andover, MA 01810 USA 1-888-778-2733 www.se.com/us  Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. Schneider Electric and Square D are trademarks owned by Schneider Electric Industries SAS or its affiliated companies. All other trademarks are the property of their respective owners. © 2012–2021 Schneider Electric All Rights Reserved

]]>
Schneider Electric LVS04665 EU RoHS Declaration Manual https://itsmanual.com/schneider/lvs04665-eu-rohs/ Tue, 27 Jun 2023 18:19:55 +0000 https://itsmanual.com/?p=130688 Read More...

]]>

Schneider Electric LVS04665 EU RoHS Declaration Declaration

Product Information

The Linergy BS is a switchgear product from Schneider Electric that is subject to IEC 61439-1 & 2 certification. This product is designed to be fitted in a PrismaSeT switchboard only and must be installed, operated, serviced, and maintained only by qualified personnel.

Product Usage Instructions

  1. Ensure that the Linergy BS is being fitted in a PrismaSeT switchboard only.
  2. Installation, operation, servicing, and maintenance of this product should be carried out by qualified personnel only.
  3. Refer to the instructions provided in the user manual for fitting the Linergy BS in a PrismaSeT switchboard.
  4. Before installation, ensure that the electrical equipment is de-energized and all safety precautions are taken.
  5. Familiarize yourself with the Linergy BS product specifications, including its Icw (kA eff. / 1 s) and IP ratings, as listed in the user manual.
  6. Use the appropriate tools and materials for installation and follow the torque values specified in the user manual for tightening connections.
  7. Contact Schneider Electric for any queries or concerns regarding the installation, operation, servicing, or maintenance of the Linergy BS product.

PRODUCT OVERVIEW

BOX CONTENTS

PLEASE NOTE

  • Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
  • No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

WARNING
PrismaSeT switchboards equipped with the Linergy busbar connection system and Schneider Electric switchgear are subject to IEC 61439-1 & 2 certification. The instructions in this document describe how to fit Linergy in a PrismaSeT switchboard.
The installer is fully liable if it is fitted in any other switchboard.

Instructions

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.

This document has been printed on ecological paper.

Schneider Electric Limited
Stafford Park 5
Telford, TF3 3BL
United Kingdom
www.se.com/uk
© 2021 Schneider Electric – All rights reserved.

]]>