SYSTXCCITW01–A, SYSTXCCITN01–A & SYSTXCCITC01–A Infinityr Touch Control
Installation Instructions
NOTE: Read the entire instruction manual before starting the installation.
US Patents: Carrierr® U.S. Pat No. 7,243,004, Carrierr® U.S. Pat No. 7,775,452, pointSET™ U.S. Pat No. 7,415,102
Safety Considerations
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this HVAC system. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings and cautions included in literature and attached to the unit. Consult local building codes and the current edition of the National Electrical Code (NEC) NFPA 70. In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1.
Recognize safety information. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING,andCAUTION. These words are used with the safety–alert symbol. DANGER identifies the most serious hazards, which will result in severe personal injury or death. WARNING signifies hazards, which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions that will result in enhanced installation, reliability, or operation.
Introduction
The Infinityr® System consists of several intelligent communicating components which include the Infinityr® Touch Control (or User Interface), variable speed furnace or FE fan coil, and 2–stage AC or HP, which continually communicate with each other via a four-wire connection called the ABCD bus. Commands, operating conditions, and other data are passed continually between components over the ABCD bus. The result is a new level of comfort, versatility, and simplicity.
All Infinityr® furnaces or fan coils are variable–speed and multi-stage for maximum flexibility, efficiency, and comfort. They support controlled ventilation, humidification, dehumidification, and air quality control. Either an Infinityr (communicating), or a standard single-stage 24VAC controlled outdoor unit may be used.
When using conventional single-stage outdoor units, the Infinity furnace or fan coil provides the 24-volt signals needed to control them. Also, the Infinityr® Network Interface Module (P/N SYSTXCCNIM01) allows the connection of a Carrier HRV or ERV without the need for separate wall control.
When using a Carrier HRV or ERV with a zoned system, the Infinityr® Zone board allows connection of a Carrier HRV or ERV without the need for separate wall control.
All system components are controlled through the wall-mounted Infinity Touch Control, which replaces the conventional thermostat and provides the homeowner with a single wall control for all features of the system.
Quick Start
Set Time and Date
From the main screen, touch MENU, on the bottom of the control. The TIME/DATE icon allows you to set the time and date for the Infinityr® Touch Control.
- To set the HOUR, MINUTE, MONTH, DAY, or YEAR touch the feature you wish to change.
- Use the Up () and Down () buttons to make the appropriate changes.
- When you have completed all of the settings touch SAVE.
- If you make a mistake you may touch CANCEL and begin again.
Set Dealer Information
From the main screen, touch MENU, on the bottom of the control. The SERVICE icon allows you to upload your contact information into the Infinity Touch Control.
A12176
- Format your contact information and logo (if applicable) using the PC/MAC application, save it to a standard USB drive. See Section 6.7.
- Touch the SERVICE icon for about 10 seconds, then touch DEALER LOGO UPLOAD.
- Place the USB drive into the USB port on the bottom of the Infinity Touch Control and follow the on screen prompts.
- More detailed information can be found on HVACPartners.com under the Product tab> Thermostats & Controls> SYSTXCCITW01> Documents & Downloads> Marketing/Miscellaneous> Infinity Touch Control Dealer Logo Application — Instructions.
Installation
Overview
This instruction covers installation of the Infinityr® Touch Control and the Infinityr Wireless Access Point only. Physical installation instructions for the indoor and outdoor equipment, and accessories are provided with each unit.
Setup, commissioning, operation, and troubleshooting of the Infinityr® System are covered only in this installation instruction. It is the guide to connecting the system components and commissioning the system once all physical components are installed. Special screen prompts and start-up capabilities are provided in the Infinityr® System to simplify and automate the initial commissioning of the system.
- Install the Infinity Touch Control according to this instruction.
- Install indoor unit, outdoor unit, and accessories according to their instructions.
- Wire complete system according to this instruction.
- Setup, commission, and operate system according to this instruction to assure a smooth and trouble-free startup.
Check Equipment
Inspect equipment. File a claim with shipping company prior to installation if shipment is damaged or incomplete.
Location
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect power before routing control wiring.
All wiring must comply with national, local, and state codes.
Wall Control
The Infinity Touch Control is the command center for the Infinity System. It should be located where it is easily accessible and visible to the adult homeowner or end-user. For accurate temperature measurement, the following guidelines should be followed:
The Infinity Touch Control and Remote Room Sensors SHOULD be mounted:
- Approximately 5–ft (1.5 m) from the floor.
- Close to or in a frequently used room, preferably on an inside partitioning wall.
- On a section of wall without pipes or ductwork.
The Infinity Touch Control and Remote Room Sensors SHOULD NOT be mounted:
- Close to a window, on an outside wall, or next to a door leading to the outside.
- Exposed to direct light or heat from a lamp, sun, fireplace, or other temperature–radiating objects which could cause a false reading.
- Close to or in direct airflow from supply registers.
- In areas with poor air circulation, such as behind a door or in an alcove.
Remote Room Sensors
A Remote Room Sensor can be used with the Infinity Touch Control to take the place of the control’s internal temperature sensor. This allows the Infinity Touch Control to be mounted in areas with less than optimal airflow (such as near an exterior door, window or in a closet). The remote sensor can be wired to the terminal block connectors labeled S1 and S2 at the control’s backplate, or the ZS1 and ZS1C connection at the Damper Control Module. In either case, the Infinity Touch Control will automatically detect the Remote Room Sensor and ignore its internal temperature sensor.
Remote Room Sensor Averaging
Typically, one remote sensor is used but, multiple sensors may be used and averaged in some applications. Averaging requires a special series-parallel wiring method with a specific number of sensors. See figure below. It is also important to note the humidity sensor cannot be remotely located, so do not locate the Infinity Control in an area where humidity sensing may not be accurate.
Smart Sensors (for zoning applications)
Any zone may use a Smart Sensor. It provides a temperature display and buttons to adjust the desired temperature in that zone only. It also displays outdoor temperature and indoor humidity sensed at the control. Only one Smart Sensor may be used per zone. They cannot be averaged like Remote Room Sensors. If a Smart Sensor is used in a zone, a Remote Room Sensor may also be used in the same zone. The Remote Room Sensor has priority over the Smart Sensor. The Smart Sensor will display the Remote Room Sensor temperature.
NOTE: Smart Sensors must be addressed to identify which zone it will control. See Smart Sensor Installation Instructions for details.
Wiring Considerations
Ordinary thermostat wire is recommended. Use 22 AWG or larger for normal wiring applications. Continuous wire lengths over 100 ft. should use 20 AWG or larger.
NOTE: ABCD bus wiring only requires a four-wire connection; however, it is good practice to run thermostat cable having more than four wires in the event of a damaged or broken wire during installation.
Each communicating device in the Infinityr Zone System has a four-pin connector labeled ABCD. It is recommended that the following color code be used when wiring each device:
A — Green = Data A
B — Yellow = Data B
C — White = 24VAC (Com)
D — Red = 24VAC (Hot)
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing the system, the main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lockout and tag switch with a suitable warning label.
- Turn off all power to equipment.
- If an existing Infinityr Control or other control is being replaced:
- Remove existing control from wall.
- Disconnect wires from existing control.
- Discard or recycle old control.
- NOTE: Mercury is a hazardous waste, if existing control contains any mercury, it MUST be disposed of properly. The Infinity Touch Control does not contain mercury.
- Select Infinity Control mounting plastic (backplate and decorative backplate if desired).
- Route wires through large hole in mounting plastic. Level rear plastic against wall (for aesthetic value only; Infinity Touch Control need not be level to operate properly) and mark wall through two mounting holes.
- Drill two 3/16–in (4.8 mm) mounting holes in wall where marked.
- Secure mounting plastic to wall using two screws and anchors provided.
- Adjust length and routing of each wire to reach each wire entry on the connector backplate. Strip 1/4–in (6.4 mm) of insulation from each wire.
- Match and connect thermostat wires to proper terminals on control backplate.
- See wiring diagrams in Appendix A.
- Push any excess wire into the wall. Seal hole in wall to prevent any air leaks. Leaks can affect operation.
- Attach Infinity Control to the mounting plastic by lining up the plastic guides on the back of the control with the opening on the mounting plastic and push on.
- Perform installation of all other system equipment (i.e. dampers, humidifier, ventilator, UV lights, etc.).
- Turn on power to equipment.
Shielded Wire
If the thermostat wiring will be located near or in parallel with high voltage wiring, radio, TV, or Ethernet wiring, then four-conductor, twisted–pair, shielded cable can be used to reduce or eliminate potential interference. The shield wire should be connected to the C terminal, or ground, at the indoor unit. The shield wire should NOT be connected to any terminal at the user interface. Connecting the shield to the ground at both ends can cause current loops in the shield, reducing shield effectiveness.
Connect one pair of the two–pair (minimum) cable to the A and B communication terminals, and another pair to the C and D terminals at both ends of the cable. The shield wire should ONLY be connected at the indoor equipment ground or C terminal. Note that some outdoor units only require the A and B connections. See the outdoor unit installation instructions for more information.
Damper Control Module (zoning systems only)
All wiring is run back to the Damper Control Module. Select a location near the furnace or fan coil where wiring from the control, each Remote Room Sensor or Smart Sensor, each damper actuator, and the equipment itself can come together easily. The Damper Control Module is approved for indoor use only and should never be installed with any of its components exposed to the elements. The Damper Control Module (and zone dampers) may be installed in any area where the temperature remains between –4°F to 158° F (–20° C to70° C), and there is no condensation. The cover must be installed to prevent damage from other sources.
Do not locate where it will be accessible to children. It may be mounted in either vertical or horizontal position. Remember that wiring access is likely the most important consideration.
CAUTION
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
To prevent possible damage to the Damper Control Module, DO NOT mount on plenum, ductwork, or flush against furnace or fan coil.
Mounting
First become familiar with all plastic assembly pieces shown on the following page. The Infinity Touch Control will snap together with the backplate. A backplate is supplied. Attach backplate using only a small hole in the wall allowing a four-wire connection to pass through. Mount the assembly to the backplate.
NOTE: Once Infinity Control is secured to wall with the backplate assembly (snapped together), care must be taken not to bend or break the interlocking tabs
when removing.
Decorative Backplate
Sold separately, a thin decorative backplate is available to hide any marks/screw holes left from the previous thermostat. This decorative backplate (or beauty ring) is used by snapping it onto the back of the mounting plate before securing the plate to the wall.
A12213
NOTE: Once the Infinity Touch Control is secured to wall with the backplate assembly (snapped together), care must be taken not to bend or break the interlocking tabs when removing.
Humidifier Connections
A 24VAC bypass or fan powered humidifier may be installed.
NOTE: Do NOT use a traditional humidistat to control humidifier operation. If a humidifier is installed, let the Infinity Touch Control operate humidifier.
Bypass Humidifier
A bypass humidifier should be wired directly to the furnace or fan coil HUM and 24VAC COM terminals. The Infinity Control Touch will automatically energize the HUM output during a call for humidification.
Fan Powered Humidifiers
Most fan-powered humidifiers produce internal 24VAC in order to energize upon a switch or contact closure. For this application, a 24VAC N.O. Isolation Relay (DPST) MUST be used to prevent mixing the internal humidifier power with the indoor equipment transformer. Applying 24VAC isolation relay coil to furnace or fan coil HUM and COM terminals will allow the Infinity Touch Control to automatically energize the HUM output during a call for humidification. The N.O.
relay contacts will be used to energize the humidifier. See fan-powered humidifier installation instructions for more details.
Commissioning
This section addresses initial power-up (or commissioning) of a new Infinity® Touch Control. The control will communicate and identify all components in the
Infinityr® System. The following is a typical example for a communicating variable–speed furnace/fan coil with a 2–stage air–conditioner/heat pump (including HYBRIDHEAT® dual fuel system).
Searching for Indoor Unit
The Infinity Touch Control will light up and begin the commissioning process by displaying “Searching for indoor unit”. This includes Infinityr® small packaged products (SPP), with UI Version 8.0 software or later.
A12177
NOTE: If the Infinity–compatible indoor equipment (furnace or fan coil) cannot be found, the control will display “Indoor unit not found”. This MUST be corrected before the initial power-up sequence can continue. Proceed to the next section, Searching for an outdoor unit. If it is not corrected, the Infinity Touch Control will go into its DEMO operating mode.
Searching for Outdoor Unit
The Infinity Touch Control will then proceed to communicate with the outdoor unit by displaying “Searching for outdoor unit”. This includes Infinityr small packaged products (SPP), with UI Version 8.0 software or later.
NOTE: If the outdoor unit cannot be found, the control will display “Outdoor unit not found”.
- Select the appropriate unit installed; then, touch NEXT.
- AC1Stage – 1–stage air conditioner
- *AC2Stage – 2–stage air conditioner
- *HP1Stage – 1–stage heat pump
- *HP2Stage – 2–stage heat pump
- None – No outdoor unit installed
NOTE: For small packaged products (SPP), the selection screen is not needed and will not appear.
- The installer will first be instructed to select the appropriate size of the outdoor unit; then, touch SELECT.
*Network Interference Module (NIM) may be required for these selections to be displayed.
Indoor Evaporator Selection
If a furnace is installed with a variable-capacity heat pump, a screen will appear to select the installed indoor evaporator coil. This selection is used to adequately calculate the refrigerant charge required while in the heat pump charging screens under the Heat Pump Checkout menu (See page 44). Select “other” for non–Carrier evaporators.
Electric Heater Selection
If the indoor equipment is a fan coil, the control will display “Searching for heater” until one is found. If the electric heater is not self–identifying, the select heater screen will appear. Touch the appropriate heater size; then, touch SELECT.
Hydronic Heat Application
The Infinity Touch Control supports 2 types of Hydronic Heat applications:
- Hot water coil in combination with an FE fan coil and heat pump, or hot water coil as sole heat source with an FE fan coil.
- Non–zoned FE fan coil combined with radiant hot water heat.
In either application, a Hydronic Heat kit should be installed in place of an electric heater. See FE fan coil Product Data for accessory part number. The system will self–identify that hydronic heat has been installed during electric heater selection.
The system will treat the hot water coil as either auxiliary heat in a heat pump application, or the sole heat source. Setup options for Hydronic Heat applications are described in the setup section of this instruction.
A13117
Searching for SAM Module (If Applicable)
“Searching for SAM Module” will appear on the screen to determine if a System Access Module, used for home automation only, is connected to the system.
NOTE: For more information regarding the SAM Module, reference the latest version of the application specification entitled “Carrier Communicating HVAC System” (Version 2 or later), available on HVACpartners.com, or the System Access Module Installation Instructions.
Searching for Zones (If Applicable)
“Zoning — Searching” will appear on the screen to determine if any zones are present. The screen will show Zone 1, Zone 2, etc., and indicate all zones having either a Remote Room Sensor, or smart sensors associated with them. If the system contains smart sensors, they must be assigned a zone number before continuing. See the Smart Sensor Installation Instructions on how to assign Smart Sensors to their respective zones. After each zone has been identified, touch NEXT.
Filter Type Selection
The installer will next be prompted to select the air filter type installed with the
Infinity System. After the selection is made, touch NEXT.
- Air Filter: 1–in. to 4–in. media filter
- EAC: high voltage electronic air cleaner
- Air Purifier: Infinityr® or Performancet™ Air Purifier
Humidifier Installation
Next, the installer will be prompted to select whether a humidifier is installed in the system. Select YES or NO, then touch NEXT.
Ultraviolet Lights Installation
Next, the installer will be prompted to select whether ultraviolet lights are installed in the system. Select YES or NO, then touch NEXT.
Equipment Summary
The equipment summary screen will appear after accessories have been selected.
This screen will give a summary of all equipment automatically found or manually selected. If an incorrect selection was made, touch REINSTALL to restart the
installation process.
Static Pressure Check
The static pressure check screen will appear next. The system will perform a static pressure check. This process will take about 1–1/2 minutes to complete. When completed, a screen will appear displaying the static pressure (in inches) across the equipment at the expected highest delivered airflow. If the blower RPM is greater than 1200, then a warning will appear, but equipment operation and the TrueSenset™ dirty filter detection operation will not be affected. When the static pressure check is complete, touch NEXT. NOTE: The static pressure check occurs only at initial installation, or when INSTALL isrunintheINSTALL/SERVICE menu.
Duct Assessment (zoning applications only)
The duct assessment screen will be displayed next for zoning applications. Touch NEXT to start Duct Assessment. Duct Assessment will measure the relative size of the ductwork, up to and through the dampers. These measurements are used to control the correct amount of airflow in the zoned system. Status messages will appear on the screen to indicate what the system is doing. The process will take approximately one minute per zone. The duct assessment will override a call for heat or cool.
A duct assessment will automatically occur each day at a user-selectable time. The factory default time is 1:00 p.m. but, may be changed by entering the Zoning Setup menu (see pages 36 — 37). If there is an active call for heating or cooling, the system will wait until the call is satisfied before it performs the duct assessment. The system will first open all zones and drive the blower to 175 CFM/ton of cooling (or the minimum indoor unit’s airflow, whichever is greater). It will then take a static pressure measurement. The system will then close all zones and open one zone at a time, taking a static pressure measurement for each zone.
The system will then close all zones and take a pressure measurement, getting a value for the duct leakage up to and through the dampers. With these static pressure measurements, the system will calculate the relative size of each zone as well as the percent leakage through the dampers At the end of the process, the display will show the relative size of each zone duct.
If the Infinity Touch Control detects an error (damper not moving or damper wired backward), it will perform the duct assessment again. If it still detects a damper problem, it will default the measurements into equal sizes, with 10% leakage, and display the zone number for the suspected zone damper. After the duct assessment is complete, touch NEXT.
Service Menu
The Service menus contain a set of vital information. This information enables the installer or service person to view a summary of what has been installed, etc. This information is not covered in the Owner’s Manual.
To enter service menus, touch menu, then touch and hold the SERVICE icon for at least ten seconds. The following screens are available in installation and service. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
NOTE: See the Owner’s Manual for information regarding software upgrades.
Equipment Summary
Touch EQUIPMENT SUMMARY to show indoor unit type and model number, outdoor unit type (and model number if a 2–stage unit), filter type, any accessories that are installed, and the number of zones in the system. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
Installation
Touch INSTALLATION to perform the start-up process in order to learn all equipment in system. Press right side button to initiate the process. Touch NEXT to begin the process.
Touch Duct Assessment to perform a duct assessment. This can be done if duct modifications have been made since the installation of the UI. Duct assessment can be performed without performing a full system install.
A12146
NOTE: For Small Packaged Products (SPP), please use the following instructions for Set–up (Section 6.3), Checkout (Section 6.4), and Service (Section 6.5):
–For PAC AC Indoor and OAC HP Indoor, follow Fan Coil instructions.
–For Gas PAC Indoor and Gas PHP Indoor, follow Furnace instructions.
–For all PAC Outdoor, follow AC/Heat Pump instructions.
Set up
NOTE: Depending upon the equipment installed, the following options will be displayed.
- Indoor:
- Furnace
- Fan coil
- PAC AC Indoor
- PAC HP Indoor
- GAS PAC Indoor
- GAS PHP Indoor
- Outdoor:
- AC/Heat pump
- PAC AC outdoor
- PAC HP outdoor
- GAS PAC outdoor
- GAS PHP outdoor
Once the equipment has been selected, the appropriate menus will be displayed.
Thermostat
First touch SETUP, then touch THERMOSTAT to set up the parameters for the Infinity® Touch Control.
Auto Mode set up
Once the auto changeover option has been selected, touch SAVE.
- Enable or Disable: Choose to enable or disable auto changeover mode
- Default = Enable
- Auto changeover time: Adjustable from 5 to 120 minutes
- Default = 30 minutes
Heat/Cool Deadband
The minimum difference enforced between heating and cooling desired temperatures. The deadband does not change when the user changes between Fahrenheit (°F) and Celsius (°C). Ex: A 2° deadband will be 2°For2°Canddoes not change with units, °Fand °C. This can allow one setting to “push” the other to maintain this difference. When the correct deadband is set, touch SAVE.
- Deadband: Adjustable from 0 to 6° F
- Default = 2°
Offsets
This option allows calibration (or deliberate miscalibration) of the temperature and humidity sensors. These offsets are added to the actual temperature/humidity
values. When the correct offsets are made, touch SAVE.
- Outdoor temperature: Adjustable from –5 to 5°F(-3to3°C)
- Default = 0°F
- Humidity: Adjustable from –10 – 10%
Reset factory defaults
This option allows the installer to reset certain factory parameters. After the selections are made, touch SAVE.
- Program Schedule: Reset back to pre-programmed time and temperature.
- User Settings: Reset user settings back to pre-programmed values.
- Install Settings: Reset installation settings back to pre-programmed values.
- Last 10 Faults: Reset the last 10 system faults under the Service menu.
Scheduling Enable
This option lets the installer allow programming features. After the selection is made, touch SAVE.
- Scheduling: On or Off
- Default = On
Smart Recovery Enable
Applies to programmable operation only. Will start recovery 90 minutes prior to scheduled change in both heating and cooling mode. After the selection is made,
touch SAVE.
- Smart Recovery: On or Off
- Default = On
NOTE: The “Temperature Units Display” set–up section has been moved to the Homeowner Screens. See the Owner’s Manual for more information.
Fan Coil
First touch SETUP, then touch FAN COIL to set up the parameters for the fan coil unit.
A12188
Airflow
This option allows the installer to select the appropriate airflow based on the needs of the installation. The QUIET airflow means the minimum cooling airflow that the system can safely run (typically 300 CFM/ton). Use this setting if duct noise is a severe problem. Note that duct sweating in high humidity environments could become an issue at low airflows. The COMFORT airflow means airflow is varied depending on humidity and temperature demand settings. This selection enables the full dehumidify and comfort capabilities of the system. The EFF325 airflow is a fixed airflow used to achieve specified ratings – no dehumidification airflow reduction is performed. This is nominally 325 CFM/ton, but will vary if a 2–stage outdoor unit is used. The EFF350 airflow is a fixed airflow used to achieve specified ratings – no dehumidification airflow reduction is performed. This is nominally 350 CFM/ton, but will vary if a 2–stage outdoor unit is used. The MAX airflow is a fixed 400 CFM/ton. No dehumidification airflow reduction is performed.
The dehumidify airflow, when set to NORMAL, is allowed to adjust to a minimum to satisfy the dehumidification call. When set to HIGH, the minimum airflow during the dehumidify mode is increased to reduce duct and register to sweat. Also, the airflow increases minimum airflow during normal cooling operations to help reduce duct sweating.
After the selections are made, touch SAVE.
- Cooling Airflow: Quiet, Comfort, EFF325, EFF350, or Max
- Default = Comfort
- Dehumidify Airflow: Normal or High
- Default = Normal
Altitude
- Static Pressure selection: 0 to 10,000 feet. This is used to correct the static pressure readings the system performs.
Fan Coil Dehumidification
The Dehum Drain Time option turns off the continuous fan at the end of cooling for five minutes in order to drain the indoor coil of water. The fan will only be turned off if a dehumidify demand existed at the start of or during the cooling cycle.
The Electric Reheat option enables the electric heat to be used while cool–to–dehumidify is running. This will allow the cool–to–dehumidify function to run longer, greatly improving humidity control in cooling mode. Accumulated electrical energy used while reheating (in kilowatt-hours) is shown on the Fan Coil Run Hours screen and can be reset there. This option is only available with fan coil systems.
After the selections are made, touch SAVE.
- Dehum Drain Time: Adjustable from 5 to 60 minutes or OFF
- Default = 15 minutes
- Electric Reheat: Yes or No
- Default = No
Fan Coil G–Terminal
This setup option selects desired operation when the R to G contact is closed on the fan coil control board. Under this function option, fan turns on fan to the selected fan speed when G terminal is energized. Use the alert function to select the contact state for an alert. Select Normally Open or Normally Closed, and then save your selection. Shutdown shuts off fan and equipment when initiated. After the selections are made, touch Save.
A13229
Fan Coil G–Terminal Alert
Use the alert function to select the contact state for an alert. Select Normally Open or Normally Closed, and then save your selection.
A13230
Shutdown: This setup option selects the change of state required for the shutdown. Select Normally Open or Normally Closed, and then save your selection.
A13231
Furnace
First touch SETUP, then touch FURNACE to set up the parameters for the furnace unit.
Furnace Airflow
Selects the airflow of the furnace when heating. EFFICIENCY is the airflow used to meet specified ratings, COMFORT is a decreased airflow used to increase the output air temperature and provide increased comfort.
For the Low heat rise option, set to ON if the system contains a bypass humidifier.
The ON setting will increase the furnace low heat airflow.
After the selections are made, touch SAVE.
- Furnace Air Flow: Comfort or Efficiency
- Default = Comfort
- Low Heat Rise: On or Off
- Default = Off
AC/HP Air Flow
This option elects the airflow of the furnace when cooling, heat pump heating, and dehumidification.
The QUIET airflow means the minimum cooling airflow that the system can safely run (typically 300 CFM/ton). Use this setting if duct noise is a severe problem. Note that duct sweating in high humidity environments could become an issue at low airflows. The COMFORT airflow means airflow is varied depending on humidity and temperature demand settings. This selection enables the full dehumidify and comfort capabilities of the system. The EFF325 airflow is a fixed airflow used to achieve specified ratings – no dehumidification airflow reduction is performed.
This is nominally 325 CFM/ton but will vary if a 2–stage outdoor unit is used. The
EFF350 airflow is a fixed airflow used to achieve specified ratings – no dehumidification airflow reduction is performed. This is nominally 350 CFM/ton but will vary if a 2–stage outdoor unit is used. The MAX airflow is a fixed 400 CFM/ton. No dehumidification airflow reduction is performed.
The dehumidify airflow, when set to NORMAL, the airflow is allowed to adjust to a minimum to satisfy the dehumidification call. When set to HIGH, the minimum airflow during the dehumidify mode is increased to reduce duct and register to sweat. Also, the airflow increases minimum airflow during normal cooling operations to help reduce duct sweating.
After the selections are made, touch SAVE.
- Cool: Quiet, Comfort, EFF325, EFF350, or Max
- Default = Comfort
- HP Heat: Comfort or EFF350
- Default = Comfort
- Dehumidify: Normal or High
- Default = Normal
Furnace Staging
This option controls the staging of the furnace and selects the minimum amount of time low stage must operate before high stage is activated. SYSTEM setting will allow the Infinity Zone Control to determine furnace staging. LOW will only run the low stage of furnace heat. LOW–MED will run the low and medium stages (2 stages of heat). MED will only run the medium stage of heat. MED–HIGH will run the medium and high stages (2 stages of heat). HIGH will only run the high stage of furnace heat.
NOTE: Two-stage furnace has LOW and HIGH selections only.
- Stages: System, Low, Low–Med, Med, Med–High, or High
- Default = System
Furnace Airflow Limits (modulating furnace only)
The following settings allow the installer to restrict the furnace within certain minimum and maximum airflows. These airflows are converted to capacities. The Min and Max limits are determined by the equipment size. These settings are not the same as the zoning airflow limits.
- Min. modulating limits: Minimum CFM to run a modulating furnace. This will increase the minimum operating capacity of the furnace.
- Default value is the furnace airflow for the lowest heat capacity.
- Max. modulating limits: Maximum CFM to run a modulating furnace. This will increase the maximum operating capacity of the furnace.
- Default value is the furnace air flow for the highest heat capacity
Furnace Off Delay
This option denotes the amount of time the blower will continue to run after heating has shut off. After the selection is made, touch SAVE.
- Furnace Off Delay: 90, 120, 150 or 180 seconds
- Default = 120 seconds
Altitude
For gas de–rating, this setting will adjust the furnace’s airflow to compensate for altitude. Altitude adjustment is not available with older furnaces. Please see furnace instructions for further details. After the selection is made, touch SAVE.
- Altitude: 0000 – 2000, US 2001 – 3000, CN 2100 – 4500, US 3001 – 4000, US 4001 – 5000, US 5001 6000, US 6001 – 7000, US 7001 – 8000, US 8001 – 9000, and US > 9000.
- Default = US 2001–3000
- Static Pressure selection: 0 to 10,000 feet. This value is used to correct the static pressure readings the system performs.
Furnace Dehumidifier Drain
This option selects the time the continuous fan turns off at the end of cooling in order to drain the indoor coil of water. The fan will only be turned off if a dehumidify demand existed at the start of or during the cooling cycle.
- Dehumidify Drain Time: Adjustable from 5 to 60 minutes
- Default = 15 minutes
Furnace G Terminal
This setup option selects desired operation when the R–G circuit changes state on the furnace control board depending on setup.
Under the function option, FAN turns on fan to selected fan speed when G terminal is energized. SHUTDOWN shuts off fan and equipment when initiated.
After the selections are made, touch SAVE.
- Function: Disabled, Fan or Shutdown
- Default = Disabled
- Fan Speed:Low,Med,orHigh
- Default = Low
- Shutdown:
- Normally Open
- Normally Closed
- The shutdown function may not be immediate. Blower off delays, etc., will still be used. The shutdown is not intended for commercial applications. If immediate shutdown is required, provision must be made to remove power to indoor unit.
Furnace G–Terminal Alert
Use the alert function to select the contact state for an alert. Select Normally Open or Normally Closed, and then save your selection.
A13230
Shutdown: This setup option selects the change of state required for shutdown.
Select Normally Open or Normally Closed, and then save your selection.
AC/Heat Pump
First touch SETUP, then touch AC/HEAT PUMP to set up the parameters for the AC/Heat Pump unit.
A12190
Latching
High Cool Latch
- System in Control
- The system will decide which stage should be running to satisfy the cooling demand.
- High Cool
- Temperature above which only the high stage of cooling will be energized.
- Only Low Cool
- The system will only run in low-stage cooling.
High Heat Latch
A13228
- System in Control
- The system will decide which stage should be running to satisfy the heating demand.
- High Heat
- Temperature below which only the high stage of heating will be energized.
- Only Low Heat
- The system will only run in low-stage heating.
Cooling Lockout
Outside temperature below which cooling will not be provided. After the selection is made, touch SAVE.
- Cooling Lockout Temp: None, 45, 50 or 55 (_F)
- Default = None
Defrost Interval
Time interval at which defrost cycles can occur on a heat pump. AUTO means the defrost interval is optimized by the outdoor control. After the selection is made, touch SAVE.
- Set Defrost Interval: 30, 60, 90, 120 minutes or AUTO
- Default = 30 minutes
Low Ambient Cooling
Selecting YES will enable the low ambient cooling operation in the outdoor unit. This setting is only available with communicating outdoor units and with Cooling Lockout set to NONE. Low ambient kits are not needed with communicating outdoor units. After the selection is made, touch SAVE.
- Low Ambient Cooling: Yes or No
- Default = No
Quiet Shift
This option turns on Quiet Shift function in 1–stage or 2–stage communicating heat pumps. After the selection is made, touch SAVE.
NOTE: This option is not available with variable speed heat pumps.
- Quiet Shift:OnorOff
- Default = Off
AC/Heat Pump RPM Max
Used with variable capacity heat pumps, this option clamps the operating speed of the heat pump to this maximum. Used to reduce operating noise while in high heating capacity. Reducing this value will reduce the heating capacity of the heat pump. After the selection is made, touch SAVE.
- AC Heat Pump Max RPM: Adjustable from 4500 – 7000
- Default = 4500 RPM
Defrost Fan Delay
Turns on the outdoor unit fan at the end of a defrost cycle for approximately 12 seconds. This helps to reduce any nuisance refrigerant noise caused by the switching reversing valve. This setup is only available on communicating heat pumps. After the selection is made, touch SAVE.
- Defrost Fan Delay: Yes or No
- Default = No
Brownout Disable
This option turns off the high voltage brownout detection function in the outdoor unit control. After the selection is made, touch SAVE.
- Brownout Disable: On or Off
- Default = Off
Energy Efficiency
This option is used to input the published ratings of the installed air conditioner or heat pump as part of the energy tracking calculation. After the ratings are entered, touch SAVE.
Heat Source Lockout
First touch SETUP, then touch HEAT SOURCE LOCKOUTS to set up the parameters for the AC/Heat Pump unit.
For hydronic heat applications, this option allows the installer to set the lockout temperatures below which only the hydronic coil will operate, and the lockout temperature above which the hydronic coil will not operate. After the selections are made, touch SAVE.
A12149
- HP Lockout: Adjustable from 5 to 55°F(–15to13°C) or None
- Default = None
- Furnace, Electric Heat or Hydronic Lockout: Adjustable from 5 to 55°F (–15to13_C) or None
- Default = None
- Defrost with Furnace, Electric Heat or Hydronic: Yes or No
- Default = Yes
Zoning (If Applicable)
First touch SETUP, then touch ZONING to set up the parameters for the zoning system (if applicable).
Zoning Disable
This option allows the installer to enable or disable zoning. After the selection is made, touch SAVE.
- Disable Zoning: Yes or No
- Default = No
Zone Offsets
This option allows actual temperature offset for each zone, allowing calibration (or deliberate miscalibration) of each sensor. Use the Left (<) or Right (>) buttons to change the zone. After the selection is made, touch SAVE.
- Temperature Offset: Adjustable between –5 to 5_F(–3to3_C)
- Default = 0_F
Zone Airflow Limits
Since a bypass damper is prohibited in this system, this setting is used to select the maximum allowable noise/airflow relationship into each zone based on air noise and comfort requirements. LOW means 100% of maximum assessed airflow; MED–LOW means 138% of maximum assessed airflow; MEDIUM means 176% of maximum assessed airflow; MED-HIGH means 214% of maximum assessed airflow; HIGH means 250% of maximum assessed airflow; and NO LIMIT means the equipment does not stage down.
CFM associated with each limit is shown on the screen. Compare this value with the equipment’s low stage CFM value to ensure that equipment will run for each zone. Assessed airflow is determined as described in DUCT ASSESSMENT. After the selections are made, touch SAVE.
- Touch the zone name that you wish to change
- Select the zone to adjust airflow: Low, Med–Low, Medium, Med–High, High, or No Limit
- Default = High
Duct Assessment Time
This option allows the installer to select the time in which the duct assessment will be performed. After the selection is made, touch SAVE.
- Duct Assessment Time: Selectable between 12 AM and 11PM
- Default = 1 PM
Accessories
First touch SETUP, then touch ACCESSORIES to set up the parameters for the accessories installed with the system.
A12192
Filter
With this option, the installer has the option of selecting pressure monitoring, the type of filter installed, and the time interval for cleaning. After the selections are
made, touch SAVE.
- Pressure Monitoring (not available with Electric Air Cleaner): Enable or Disable
- Default = Enable
- Clean Interval: Selectable from 1 to 18 months
- Default = 3 months
- Filter Type: Air Filter, Electric Air Cleaner, or Air Purifier
- Filter type is selected during installation; otherwise default = air filter
Humidifier
With this option, the installer has the option of selecting whether a humidifier is installed, to humidify with the fan in low speed, and the time interval for changing the humidifier pad. After the selections are made, touch SAVE.
- Humidifier Installed: Yes or No
- Humidifier selection made during installation; otherwise default = no
- Change Pad: Selectable from 1 to 24 months
- Default = 12 months
- Humidify with Fan: Yes or No
- Default = No
Ultraviolet Lights
With this option, the installer has the option of selecting whether ultraviolet lights are installed, and the time interval for changing the ultraviolet lights. After the
selections are made, touch SAVE.
- UV Lights Installed: Yes or No
- UV Lights selection made during installation; otherwise default = no
- Change Interval: Selectable from 1 to 48 months
- Default = 12 months
Ventilator
When a ventilator is installed, the installer has the option of selecting the time interval for cleaning the ventilator. After the selections are made, touch SAVE.
- Clean Interval: Selectable from 60, 90, 120, 150 or 180 days
- Default = 90 days
Utility Curtailment
Utility Saver is used to forcing the equipment to a lower stage (low or off) when activated by the utility company, typically during peak load times. This setup is available only if the equipment has a utility saver input (refer to outdoor equipment Installation Instructions). This setup controls the response of the equipment when the utility saver input is active. DISABLED means that the curtailment function is not active. TURN OFF means the outdoor unit is to be turned off when the curtailment function is active. LOW STAGE means the outdoor unit will run in lows stage when the curtailment function is active. After the selections are made, touch SAVE.
A12193
- Cooling: Disabled, Low Stage or Turn off
- Default = Disabled
- Heat Pump: Disabled, Low Stage or Turn off
- Default = Disabled
Hydronic Airflow
This option allows the installer to select the airflow for the fan coil when paired with a hydronic coil. After the selections are made, touch SAVE.
A12194
- Airflow: Selectable between Off to Max in 50 CFM increments
- Off = 450 CFM, MAX = (odu_size in KBTU * 400) / 12)
- Default = Off
- Blower On Delay: Selectable from 0 to 240 seconds
- Default = 30 seconds
- Blower Off Delay: Selectable from 0 to 240 seconds
- Default = 0 seconds
Check out
Touch CHECKOUT to view the equipment installed in the system. Perform checkout test to make sure each piece of equipment is operating properly.
Electric Heat
If you have a fan coil with electric heaters, this menu item will allow the heaters to be exercised. With self–identifying electric heaters, three stages of electric heat are available to be exercised in any combination. Non–identifying heaters will only provide one stage of heat. After the selections are made, touch START.
- Low Heat: Selectable from 0 to 120 minutes
- Default = 5 minutes
- Medium Heat: Selectable from 0 to 120 minutes
- Default = 5 minutes
- High Heat: Selectable from 0 to 120 minutes
- Default = 5 minutes
Furnace
Make sure the furnace is properly installed.
This option allows the furnace to be exercised. First, a low heat run time and high heat run-time are selected. The furnace will execute its ignition start-up sequence.
This sequence will be displayed on the screen. After the gas valve and blower motor turn on, the screen will show the current operating status of the furnace. After the selections are made, touch START.
- Low Heat: Selectable from 0 to 120 minutes
- Default = 5 minutes
- High Heat: Selectable from 0 to 120 minutes
- Default = 5 minutes
Hydronic
This option allows the hydronic heat relay to be exercised. First, it will energize the relay and turns on the blower. This sequence will be displayed on the screen. After the selections are made, touch START.
- Hydronic heater check: Selectable from 0 to 120 minutes
- Default = 5 minutes
Air Conditioning
This option allows the air conditioner to be exercised. With a 2–stage AC unit, a low cool and a high cool run-time are independently selectable to exercise. The display will change to show the AC operating status. After the selections are made, touch START.
NOTE: Airflows during Checkout modes are fixed to the EFFICIENCY setting and are independent of other airflow settings. To view airflows for normal air conditioning cooling mode, exit the CHECKOUT screen and apply a heating demand to the system.
- Low Cool Run Time: Selectable from 0 to 120 minutes
- Default = 5 minutes
- High Cool Run Time: Selectable from 0 to 120 minutes
- Default = 5 minutes
Heat Pump Heating
The heat pump heating mode can be exercised with this menu option. With a 2–stage heat pump, a Low Heat and a High Heat Run Time are independently
selectable to exercise.
For variable speed heat pumps, you can select the speed at which the heat pump will exercise.
After the selections are made, touch START.
NOTE: Airflows during Checkout modes are fixed to the EFFICIENCY setting and are independent of other airflow settings. To view airflows for normal air conditioning cooling mode, exit the CHECKOUT screen and apply a heating demand to the system.
- Low Heat Run Time: Selectable from 0 to 120 minutes
- Default = 5 minutes
- High Heat Run Time: Selectable from 0 to 120 minutes
- Default = 5 minutes
- Speed (variable speed heat pump only): Selectable from lowest available to 100%
- Default = lowest available as specified by variable speed heat pump
- Defrost: Yes or No
- Default = No
Heat Pump Cooling
The heat pump cooling mode can be exercised with this menu option. With a 2–stage heat pump, a Low Cool Run Time and a High Cool Run Time are independently selectable to exercise.
For variable speed heat pumps, you can select the speed at which the heat pump will exercise.
After the selections are made, touch START.
NOTE: Airflows during Checkout modes are fixed to the EFFICIENCY setting and are independent of other airflow settings. To view airflows for normal air conditioning cooling mode, exit the CHECKOUT screen and apply a heating demand to the system.
- Low Cool Run Time: Selectable from 0 to 120 minutes
- Default = 5 minutes
- High Cool Run Time: Selectable from 0 to 120 minutes
- Default = 5 minutes
- Speed (variable speed heat pump only): Selectable from lowest available to 100%
- Default = lowest available as specified by variable speed heat pump
Humidifier
The humidifier can be exercised On and Off with this menu option. To end the humidifier checkout, touch STOP.
- Humidifier Check: On or Off
Ventilator
The ventilator can be exercised through all of its operating speeds with this menu option. To end the ventilator checkout, touch STOP.
- Humidifier Check: High, Low or Off
Zoning (If Applicable)
Airflow Limits
Because there is no bypass damper, the zone airflow limit check will allow the installer to assess the airflow noise generated by the system providing the maximum amount of airflow to each zone. Touch AIRFLOW LIMITS: When START is touched, the selected zone’s damper will fully open, all others will close, and the indoor unit will provide the maximum airflow for that zone (as selected in SETUP — ZONING, Airflow Limits). If the airflow noise is objectionable, the installer can select a lower airflow noise limit. If the noise is not objectionable, the installer should leave HIGH selected, or even NO LIMIT.
NOTE: Selecting a lower airflow noise limit may decrease the homeowner’s comfort in that zone.
Touch the Left (<) or Right (>) buttons to change the desired zones. Once the proper airflow limits are set, touch SAVE,those zoning CHECKOUT menu.
Damper/Sensor Check
The Sensor/Damper Check allows the installer to check each zone damper for operation, as well as insure the zone sensor corresponds to that particular zone. When first initiated, the Zone 1 damper will fully open, and all other zones will close. Using the Left (<) or Right (>) buttons, the installer can select each zone and verify the damper is fully open while all other dampers remain closed.
After proper damper operation has been verified, the installer can now check and verify that each Remote Room Sensor corresponds to the proper zone damper in the same zone. For systems with remote room sensor, temporarily disconnect any other zone Remote Room Sensor (at sensor location). That zone damper will now open, while the Zone 1 damper will close.
For systems using Smart Sensors, the installer may press and hold the Hold and Mode buttons simultaneously for 3 seconds to change the zone under test. This should be done with each zone to verify that the zone sensor corresponds to that particular zone.
Once each zone has been checked, touch DONE to return to the ZONING CHECKOUT menu.
Zone Duct Assessment
This screen shows the results from the previous duct assessment. The duct assessment is performed at initial start-up and at 1 P.M. or the installer selected time each day. If another duct assessment is desired, the service technician should perform a reinstall of the system.
NOTE: A Duct Assessment will automatically occur every 24 hours at selected time to check system static and calibrate dampers.
Once the duct assessment is complete, touch DONE to return to the ZONING CHECKOUT menu.
Sensor Type
This option shows a list of all zones with corresponding sensor types.
Service Information
The Service Info menu will only show the equipment installed in the system. To enter this menu of options, touch SERVICE INFORMATION.
Advanced Diagnostics
When viewing the Service Information screen, there is a button labeled View Diagnostics, which provides the top 3 most likely root causes for the most recent fault.
NOTE: This feature is only available with compatible models. Those models are currently the FE fan coil, the modulating furnace, and the modulating heat pump.
Fan Coil Status
The fan coil status screen displays relevant information about the fan coil operation. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
Furnace Status
The furnace status screen displays relevant information about the furnace operation. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
AC Status
The AC status screen displays relevant information about the AC operation. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
A12199
Heat Pump Status
The heat pump status screen displays relevant information about the heat pump operation. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
A12200
Zoning Status
The zoning status screen displays relevant information about the zoning operation. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
A12201
Last 10 System Faults
This screen will show the last 10 events that occurred throughout the system. Each entry has the time and date incident recorded. These events are stored in the
memory of the control and are resettable in the THERMOSTAT SETUP screen under the RESET FACTORY DEFAULT selection. Each entry shows the equipment that generated the event. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
A12151
Run/Fault History
This information is stored in the equipment circuit boards (if communicating) and displayed on the control. The indoor unit and outdoor unit (if communicating) have the following histories. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
- Resettable Faults: Fault counters for each piece of equipment that can be reset.
- Cycle Counters: Number of heat/cool/power cycles the unit has performed.
- Run Times: Lifetime hours of operation in heating, cooling, and how long the unit has been powered.
A12202
Model/Serial Numbers
This menu item allows the installer to view the model number, serial number (if available), and control software version (if available) of all communicating pieces of equipment in the system, including the wall control. This information resides in the original equipment circuit board(s) from the factory. If an equipment circuit board has been replaced, the model and serial number will no longer be displayed. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
Service Phone Number
This menu item allows the installer to view the name and phone number that the homeowner can call for future service of the system. This name and phone number will appear to the homeowner whenever a service reminder pop–up message is displayed (i.e. Change Filter, etc.). To return to the previous screen, touch BACK. To exit, touch DONE. See Section 6.7.
Energy Tracking Watt Meter
This menu item allows the installer to view the energy usage of each piece of equipment connected to the system. To return to the previous screen, touch BACK. To exit the Service menus, touch DONE.
A12203
Refrigerant Charging
For variable speed heat pumps, a refrigerant charging menu is available to aid in the proper charging of the system. Enter the menu from the service screens by touching REFRIGERANT CHARGING.
A12204
Charging
Within the CHARGING screens, the installer will have the ability to enter the LINESET length and the VA PO R L I N E diameter. After the selections are made, touch NEXT.
- Lineset: Selectable from 5 to 200 feet
- Vapor line: Selectable with various diameters by using the up and down buttons
Next, the installer will enter the WEIGH-IN screen to verify the current total charge is accurate. Once the installer has confirmed, touch DONE.
Next, the installer will enter the SERVICE VALVE SUBCOOL screen. This screen will show the current liquid line subcool target (in _F). To begin the charging, touch START. If the outdoor temperatures are not in the required range, Service Valve Subcool may not be available.
Next, the installer will enter the SERVICE VALVE INFORMATION screen. The current liquid line subcool target, stabilization time, mode and speed in rpm, EXV position in percent, indoor airflow in CFM, outdoor coil temperature in _F, indoor temperature in _F, outdoor temperature in _F, compressor discharge pressure in psig, and accumulator suction pressure in psig are displayed on this screen. Once the stabilization time has expired, touch DONE.
Pump down
Because this system has an inverter-controlled compressor, suction pressure transducer, and EXV, the conventional procedure cannot be used to “pump down” and isolate the refrigerant into the outdoor unit. The control has provisions to assist in performing this function.
- Select mode to pump down in (COOL or HEAT). COOL mode allows refrigerant to be isolated in outdoor unit. HEAT mode allows the refrigerant to be isolated in indoor coil and lineset. Set desired time period.
- Default time period for procedure is 120 minutes.
- Touch START to begin the pump-down process. Unit will begin running in selected mode after a brief delay.
Evacuation
Because this system has an EXV for the heating expansion device, additional steps must be taken to open the EXV if the heat pump unit must be evacuated for service reasons. If the EXV is not open when pulling a vacuum or recovering refrigerant from the heat pump unit, extended evacuation time may be required and/or inadequate vacuum obtained. The control has provisions to open the EXV for refrigerant recovery and/or evacuation.
- Set desired time period.
- Default time period for procedure is 120 minutes.
- Touch START on UI to open the valve.
- Begin evacuation or refrigerant recovery as required for the procedure after control indicates the EXV is open. Power may be removed from heat pump after the control indicates “READY TO EVACUATE.”
Dealer Logo
Touch DEALER LOGO to upload the dealer logo and contact information from a standard USB memory device connected to the Infinityr Touch Control. The “Dealer Logo Application” PC/MAC software download available at www.MyInfinityTouch.Carrier.com/Infinity/downloads is required to properly format the dealer logo and contact information for use on the wall control.
Along with the dealer logo (if any), three lines of dealer information are provided on the wall control:
Dealer name (50 characters, max)
Dealer phone number (20 characters, max)
Dealer URL (50 characters, max)
The wall control dealer information display is 30 characters wide. Dealer names and URLs over 30 characters will be split into two lines on the display.
The PC/MAC software application to format the dealer logo and contact information can be found at:
www.MyInfinityTouch.Carrier.com/Infinity/downloads
Download the program and follow the program instructions.
Once the dealer logo and contact information have been properly loaded onto the USB memory device, insert the USB device into the bottom edge of the Infinity Touch Control. The control will prompt you whether or not to upload the dealer logo. Once complete, you will receive a confirmation that your upload was successful. If the information was not stored properly on the USB device, you will receive an error message that the dealer logo was not found. Refer back to the PC/MAC software application instructions and try again. Once the upload is complete, touch NEXT.
If you have problems, contact your distributor service manager for support.
Wireless Set–up
With the appropriate models, the Infinity® Touch Control can connect to the in-home Wi-Fi to connect the Infinity System to the Internet. The model SYSTXCCITW01 wall control comes bundled with an Infinity Wireless Access Point. This establishes an independent Infinity System Wi-Fi network. The model SYSTXCCITC01–A is intended to connect to an existing home Wi-Fi network, or to be added to an existing Infinity System Wi-Fi network. If the in-home Wi-Fi is found to be incompatible with SYSTXCCITC01–A, an Infinity Wireless Access Point (SYSTXXXGWR01) or any other compatible wireless router can be installed to establish Wi-Fi connectivity.
Please call 1–800–CARRIER for support with Wi-Fi set–up and connection to the MyInfinity Server.
The ability to remotely access and adjust the settings of the Infinity® Touch Control with the MyInfinity web and mobile applications is dependent on the compatibility of the user’s computer/network or mobile device, the Infinity Touch Control, and/or the MyInfinity web server with, and the availability of, the user’s Internet service provider or mobile device carrier service. Carrier Corporation makes no representations or warranties, express or implied, including, to the extent permitted by applicable law, any implied warranty of merchantability or fitness for a particular purpose or use, about the compatibility of the user’s computer/network, or mobile device, with the Infinity Touch Control, and/or the MyInfinity web server, with, and the availability of, the user’s Internet service provider or mobile device carrier service, or that the ability to remotely access and adjust the settings of the Infinity Touch Control will not be negatively affected by the network-related modifications, upgrades, or similar activity of the user’s Internet service provider or mobile device carrier service.
NOTE: See the Owner’s Manual for information regarding software upgrades.
SYSTXCCITC01–A Models (only)
To establish Wi-Fi connectivity to the Infinity Touch Control using the in-home router or wireless access point the wireless access point SSID and password/passkey must be known for setting–up.
A13241
- Select the WIRELESS from the menu screen
- Make sure the Wi–Fi connection is enabled, by touching ENABLED.
- Touch SETUP A WI–FI CONNECTION to begin the process.
- Next, touch SCAN FOR AVAILABLE ACCESS POINTS.
A13235
- On the next screen look for the SSID of the router/access point. After being selected, it will be outlined in faint blue. Then select NEXT.
A13236
- The selected network will show. Choose an appropriate Wi-Fi security. Usually auto-detect will correctly identify the type of security used. If the network has no security it will show as on the left, but a secured network will prompt for the Wi-Fi security key.
- If a Wi–Fi security key is shown as on the right hand picture above then select the white bar and enter the security key, then select NEXT.
- Touch in the security key area, and the keyboard will appear.
- Use the on screen keyboard to enter the Wi–Fi security key, then touch NEXT.
- The control will inform you if the connection is successful. If so, touch DONE.
- If the connection is unsuccessful, verify that the proper information has been entered before you touch RETRY. The control will go through the process again.
A13238
- After the control has connected to the network, go to www.MyInfinity.Carrier.com to register the unit and begin remote access. This requires the MAC address and serial number of the Infinity® Touch Wall Control. To find the serial number and MAC address of the Infinity® Touch Wall Control, click on Menu, Down Arrow, Wireless and View MyInfinity Info. This screen will provide the information needed on the MyInfinity website during registration.
- If you have any issues, please contact your servicing dealer.
- When the connection to the MyInfinity web server has been established, the status screen will show Connected for both Wi-Fi and the server.
SYSTXCCITW01–A Models (only)
To establish the Wi-Fi connectivity to the Infinity Touch Control through the Infinity System Wireless Access Point (TP–LINKR® Device), connect the WAN (BLUE port) connection of TP-LINK Wireless Access Point to the home’s existing router LAN port using the provided Ethernet cable. The LAN ports on the back of the TP-LINK Wireless Access Point should not be used for other devices. The Infinity (TP-LINK) Wireless Access Point should only be used for connection of the Infinity Touch Control(s) and is not intended to be used wired or wirelessly with any other devices.
A12114
- Select the WIRELESS from the menu screen
- Make sure the Wi-Fi connection is enabled, by touching ENABLED.
- Touch SETUP A WI-FI CONNECTION to begin the process.
- Next, touch SCAN FOR AVAILABLE ACCESS POINTS.
- Select the myHVACxxxxxx connection from the list, then touch NEXT (my HVAC is followed by the last 6 digits of your Wireless Access Point’s MAC address; see the label on the bottom of the TP-LINK Wireless Access Point).
A12357
- You may have to use the down arrow to scan to the next screen to find “myHVACxxxxxx”.
A12116
- Use the on-screen keyboard to enter the Wi-Fi security key, then touch NEXT.
- Touch in the security key area, and the keyboard will appear.
- The security key can be found on the back of the TP-LINK Wireless Access Point.
- The control will inform you if the connection is successful. If so, touch DONE.
- If the connection is unsuccessful, verify that the proper information has been entered before you touch RETRY. The control will go through the process again.
A12118
- If the connection is unsuccessful, verify that the proper information has been entered before you touch RETRY. The control will go through the process again.
- After your control has connected to the network, go to www.MyInfinity.Carrier.com to register the unit and begin remote access. This requires the MAC address and serial number of the InfinityR Touch Wall Control, NOT the Wireless Access Point. To find the serial number and MAC address of the Infinity Touch Wall Control, click on Menu, Down Arrow, Wireless and View My Infinityr Info. This screen will provide the information needed on the MyInfinityr website during registration.
- If you have any issues, please contact your servicing dealer.
- When the connection to the MyInfinity web server has been established, the status screen will show Connected for both Wi-Fi and the server. TP-LINK is a trademark of TP-LINK Technologies Co., Ltd.
Appendix A — Wiring Diagrams
*NOTE: Some outdoor units do not require the “C” and “D” connections. See outdoor unit Installation Instructions.
*NOTE: For SPP products, ABCD connection between Indoor and Outdoor control boards are pre-wired at the factory.
*NOTE: For new SPP installations in which the OAT Sensor is required, please refer to the SPP Installation Instructions.
A13124
Universal Four–Wire Connection
Variable-Speed
Furnace/Fan Coil
A12354
Connection Diagram for Furnace or FE Fan Coil with 1-Stage Air Conditioning
Variable-Speed
Fan Coil
A12355
Connection Diagram for FE Fan Coil with Non–communication 1–Stage Heat Pump
Zoning Connection for Communicating Indoor Unit with 2–Stage Communicating Outdoor Unit
Zoning Connection Diagram for Furnace or FE Fan Coil with Non–Communicating 1–Stage Air Conditioning
Zoning Connection diagram for FE Fan Coil with Non–communicating 1-Stage Heat Pump
G Input Wiring for Blower Operation
G Input Wiring for System Shutdown
997-011280-7-R
Infinity and HYBRID HEAT are trademarks or registered trademarks of Carrier Corporation in the United States and other countries. Other brands and product names are trademarks of their respective holders.
Copyright 2013 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Edition Date: 11/13
997-011280-7-R
Catalog No: SYSTXCCITW—07SI
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Replaces: New