Relays and Transformers 90-112 Thru 90-130 Fan Control Center manual


Relays and Transformers 90-112 Thru 90-130 Fan Control Center manual Image

Relays and Transformers 90-112 Thru 90-130 Fan Control Center Specifications Manual

Transformer and relay combination for easy installation on a 4″ X 4″ junction box.

FEATURES

  • Line voltage connections pre-wired
  • Energy limiting Class II transformer design
  • Color coded pre-stripped leads
  • Low voltage connections on terminal board

SPECIFICATIONS

UR/CUR File Number …………………………………………………………………………………….E73641

REPLACEMENT RELAY FOR FAN CONTROL CENTER

90-112 THRU 90-130 FAN CONTROL CENTER

When the fan relay transformer is energized and the thermostat completes the connection from R to G the fan relay coil energizes. Line voltage power applied to contact common path travels to selected blower speed tap. Additional terminal Y and W are isolated tie point terminals to connect thermostat wiring to compressor and furnace (if required).

NOTE: Record the lead wire color with its corresponding terminal for future reference. Unused transformer input leads must be insulated.

* Black is common with respect to transformer winding, not external circuit.