Installer system test

To perform a System Test:

Performing an installer system test

  1. Press and hold CENTER and PLUS buttons for approximately 3 seconds to enter advanced menu.
  2. Use  PLUS to go to TEST. Press Select to enter System Test.
  3. Use PLUS to change between Heat, Cool, Fan, Em Heat, or Ver (thermostat version information). Press Select.
  4. Press PLUS to turn stages on one at a time, and press MINUS to turn them off.
  5. Use the Home button to exit the System Test.

System test / System status

Test and status table

Specifications

Temperature Ranges
Heat: 40 °F to 90 °F (4.5 °C to 32.0 °C)
Cool: 50 °F to 99 °F (10.0 °C to 37.0 °C)
Working Ambient Temperature
32 °F to 120 °F (0 C° to 48.9 °C)
Operating Ambient Temperature
37 °F to 102 °F (2.8 °C to 38.9 °C)
Shipping Temperature
-20 °F to 120 °F (-28.9 °C to 48.9 °C)
Operating Relative Humidity
5% to 90% (non-condensing)
Physical Dimensions in inches (mm) (H x W x D)
4-1/16” H x 4-1/16” W x 1-5/32” D
103.5 mm H x 103.5 mm W x 29 mm D

Electrical Ratings

Electrical rating table

CAUTION: ELECTRICAL HAZARD Can cause electrical shock or equipment damage. Disconnect power before beginning installation.

CAUTION: EQUIPMENT DAMAGE HAZARD Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly

CAUTION: MERCURY NOTICE If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal.